The importance of refrigerant composition analysis became clear when contami- nated and counterfeit refrigerant 1,1,1,2-tetrafluorethane (R134a) appeared on the market. Chloromethane (R40), present in this counterfeit R134a, is found to be incompatible with aluminum surfaces in the refrigerant system. A chemical reaction takes place resulting in a pyrophoric compound upon contact with air. This applica- tion note highlights fast, on-site characterization of the refrigerant mixture using the Agilent 490 Micro GC.

方案详情

·Agilent Technologies Composition Analysis ofContaminated and CounterfeitRefrigerants Using theAgilent 490 Micro GC Abstrac: The importance of refrigerant composition analysis became clear when contami-nated and counterfeit refrigerant 1,1,1,2-tetrafluorethane (R134a) appeared on themarket. Chloromethane (R40), present in this counterfeit R134a, is found to beincompatible with aluminum surfaces in the refrigerant system. A chemical reactiontakes place resulting in a pyrophoric compound upon contact with air. This applica-tion note highlights fast, on-site characterization of the refrigerant mixture usingthe Agilent 490 Micro GC. 点击下列图标获取免费资料 Apihent Tackw