一、法规概述
标准 | 国家 | 描述 |
SMACNA HVAC Air Duct Leakage Test manual, First edition, 2012 | US | Duct construction leakage classification, expected leakage rates for sealed and unsealed ductwork, duct leakage test procedures, recommendations on use of leakage testing, types of test apparatus and test setup and sample leakage analysis. |
二、法规详情
法规内要求的计算公式如下:
Duct Class | 1/2-, 1-, 2-inwg | 3-inwg | 4-, 6-, 10-inwg |
Seal Class | C | B | A |
Sealing Applicable | Transverse Joints Only | Transverse Joints and Seams | Joints, Seams and All Wall Penetrations |
Leakage Class | |||
Rectangular Metal | 16 | 8 | 4 |
Round Metal | 8 | 4 | 2 |
Maximum air leakage is then defined as
F=CLP0.65
F = Maximum air leakage (cfm/100 ft2)
CL = Leakage class
P = Pressure (inwg)
三、细则分析
1)法规要求下的最大限值Fmax
以美国标准为例,测试时由客户提出密封等级(Seal Class)和测试压力P,
根据SMACNA标准确定Leakage Class CL,根据公式 F=CLP0.65 计算出最大泄漏率Fmax
为方便计算,提供如下测算表:
Allowable Leakage Factor (CFM/100 sq ft) | |||||||||||
Static pressure | 0 | 1 | 2 | 3 | 4 | 6 | 7 | 8 | 9 | 10 | |
CL | 1 | 0.0000 | 1.0000 | 1.5692 | 2.0423 | 2.4623 | 3.2048 | 3.5425 | 3.8637 | 4.1712 | 4.4668 |
2 | 0.0000 | 2.0000 | 3.1383 | 4.0847 | 4.9246 | 6.4096 | 7.0851 | 7.7275 | 8.3423 | 8.9337 | |
3 | 0.0000 | 3.0000 | 4.7075 | 6.1270 | 7.3869 | 9.6143 | 10.6276 | 11.5912 | 12.5135 | 13.4005 | |
4 | 0.0000 | 4.0000 | 6.2767 | 8.1694 | 9.8492 | 12.8191 | 14.1701 | 15.4550 | 16.6847 | 17.8673 | |
6 | 0.0000 | 6.0000 | 9.4150 | 12.2541 | 14.7737 | 19.2287 | 21.2552 | 23.1825 | 25.0270 | 26.8010 | |
8 | 0.0000 | 8.0000 | 12.5533 | 16.3387 | 19.6983 | 25.6382 | 28.3403 | 30.9100 | 33.3693 | 35.7347 | |
12 | 0.0000 | 12.0000 | 18.8300 | 24.5081 | 29.5475 | 38.4574 | 42.5104 | 46.3649 | 50.0540 | 53.6020 | |
16 | 0.0000 | 16.0000 | 25.1067 | 32.6775 | 39.3966 | 51.2765 | 56.6805 | 61.8199 | 66.7387 | 71.4694 | |
24 | 0.0000 | 24.0000 | 37.6600 | 49.0162 | 59.0949 | 76.9147 | 85.0208 | 92.7299 | 100.1080 | 107.2041 |
举例如下:
Static pressure : 6
CL :6
则F = 19.2287 即最大限值Fmax
2)实测管道的测试值F
QL—泄漏风量值(cfm)
Area—被测管道的表面积(ft2)
3) 判定
F
GTI 管道漏风量测试机型号DALT6900,DALT6910仪器内置以上标准,无需计算,可以直接输出判定结果,操作简单方便!
更多
限时特惠 | 万元优惠等你拿!管道漏风量测试机换新季启动
厂商
2024.07.15
GTI吉泰精密邀您参加GMP合规-验证技术创新实践大会
厂商
2024.07.11
GTI吉泰精密邀您参加2024年度ICGEB 精准医学诊断和生物医药研讨会
厂商
2024.06.19
GTI吉泰精密邀您共赴第六届深圳国际半导体技术暨应用展览会
厂商
2024.06.17