简介:2.1 Volatile Organic Sampling Train: A schematic diagram of the principal
components of the VOST is shown in Figure 1 and a diagram of one acceptable
version of the VOST is shown in Figure 2. The VOST consists of a gla简介:2.1 Volatile Organic Sampling Train: A schematic diagram of the principal
components of the VOST is shown in Figure 1 and a diagram of one acceptable
version of the VOST is shown in Figure 2. The VOST consists of a glass-lined
probe followed by an isolation valve, a water-cooled glass condenser, a sorbent
cartridge containing Tenax (1.6 g), an empty impinger for condensate removal, a
second water-cooled glass condenser, a second sorbent cartridge containing Tenax
and petroleum-based charcoal (3:1 by volume; approximately 1 g of each), a silica
gel drying tube, a calibrated rotameter, a sampling pump, and a dry gas meter.
The gas pressure during sampling and for leak-checking is monitored by pressure
gauges which are in line and downstream of the silica gel drying tube. The
components of the sampling train are described below.
2.1.1 Probe: The probe should be made of stainless steel with a
borosilicate or quartz glass liner. The temperature of the probe is to be
maintained above 130EC but low enough to ensure a resin temperature of 20EC.
A water-cooled probe may be required at elevated stack temperatures to
protect the probe and meet the above requirements. Isokinetic sample
collection is not a requirement for the use of VOST since the compounds of
interest are in the vapor phase at the point of sample collection.
2.1.2 Isolation valve: The isolation valve should be a greaseless
stopcock with a glass bore and sliding Teflon plug with Teflon wipers (Ace
8193 or equivalent).
2.1.3 Condensers: The condensers (Ace 5979-14 or equivalent) should
be of sufficient capacity to cool the gas stream to 20EC or less prior to
passage through the first sorbent cartridge. The top connection of the
condenser should be able to form a leak-free, vacuum-tight seal without using
sealing greases.
详细>